SmartPower Supply Specifications
Model | AC-Input Voltage @115VAC @230VAC |
Typical Input current at full load @115VAC @230VAC |
Max. Output Power |
Output Volt/Current |
Output Voltage Range |
||
30 W unit | Universal Input 85 to 264 VAC 47-63 Hz |
0.65A | 0.35A | 30 Watt | 24VDC / 1.25A | 23-27 Volts | |
60 W unit | 1.15A | 0.65A | 60 Watt | 24VDC / 2.5A | |||
90 W unit | 1.55A | 0.85A | 90 Watt | 24VDC / 3.75A | |||
120 W unit | Input 90-135VAC 50-60 Hz |
Input 180-270VAC 50-60 Hz |
1.84A | 1.0A | 120 Watt | 24VDC / 5.0A | 23-24.5 Volts |
240 W unit | Input 100-135VAC 50-60 Hz |
Input 200-270VAC 50-60 Hz |
3.5A | 1.8A | 240 Watt | 24VDC / 10.0A |
Output regulation: 1% with < 100 mV ripple
Programmable Current Limit: 20% - 100% of Full Load with automatic recovery upon short-circuit
CL Output: Current-within-Limit Output, PNP transistor, 24VDC @100 mA. When output current is within user programed limit, output is on(24VDC @ 100mA); Otherwise output is off (≈0VDC)
Protection: Short-circuit, overvoltage and over-temperature protection
Recommended circuit breaker: C-Curve /Slo-blo fuse 5A
Size (30W, 60W, 90W units): 3.1” H x 2” W x 4.6” Deep
(120W and 240W units): 3.1” H x 2” W x 6.0” Deep
Shock: 10G for under 12ms in the X, Y, and Z axis
Vibrations: 5 to 55Hz 2G’s for 2 hours in X, Y, and Z axis
Operating Temperature (30W, 60W, 90W units): -25°C to 60°C (-13°F to 140°F). Above 60°C(140°F): 2.5% /°C
derating up to 70°C (185°F)
(120W, 240W units): -25°C to 50°C (-13°F to 122°F). Above 50°C(122°F): 2.5% /°C derating up to 70°C (185°F)
Storage Temperature: -25°C to + 85°C max (-13°F to 185°F)
Regulatory Agency Approvals: Pending
Mounting
SmartPower power supplies are mounted on a DIN 3 type of rail (EN 50022-35x7.5 OR EN 50022-35x15). While mounting the supply, please ensure that there is a 3” free space all around the supply for unobstructed flow of air.