M2020 Die Set Control System Specifications
Power Requirements:
120VAC+/- 10%, 50-60 Hz., 40VA Exclusive of load
Operating Temperature:
-10°F to 130°F
(-23°C to 55°C)
Position Sensor:
Dual Resolver RL210 (128:1 gear) or
Linear Rod based models
INPUT/OUTPUT
Program Enable
Contact closure to customer power supply common
(Vs-), or a solid state sinking output with less than
0.8 V drop at 10mA.
Supervisor Enable
Contact closure to customer power supply (Vs+), or
10 to 28VDC logic input, sourcing output
Outputs
All outputs NPN sinking, 30VDC max @ 100mA.
Autotech offers a compatible relay output chassis
that can be used for power outputs.
UP: Energized to move the die upward
DOWN: Energized to move the die downward
|
 |
USL: Energized when upper travel limit is exceeded
LSL: Energized when lower travel limit is exceeded
DRIFT: Energized when die position is too far from
programmed position.
BW: Energized when resolver is not functioning
nor has a broken wire
UP: Energized to move the die upward
FAULT: The fault relay coil is energized when the
M1200 is operating properly.
Resolver OK
Processor OK
It is DE-ENERGIZED when a FAULT condition exists.
Remote Inputs:
Die Number:
8 bit BCD (die number 001 to 255
Contact closure to customer power supply Vs+; or
10 to 28 V logic input, (sourcing output)
Logic False: 4 VDC @ 1mA and
Logic True: 10VDC @ 10mA to 28VDC @30mA
Remote and start inputs:
Contact closure to customer power supply common
(VS-); or solid state sinkin
|
“Ready-to-install” system package part numbers |
SYS-P2020-S128:
- M2020 Complete Die Set for automatic shut height positioning of single action presses
- Dual, 128:1, RL210 resolver with 30 Feet of resolver cable
|
YS-P2022-S128:
- Die Set for Double Action press
|
SYS-P2020-SCA:
- Above with Counter Balance Control
|
SYS-P2022-SCA:
- Above with Counter Balance Control
|