M8350 Resolver Decoder BusModule Specifications
ASY-M8350-010
A complete functional Decoder consists of a Cradle (specific to the programmable controller type), a Decoder Module (ASY-M8350-01 0), and a Filler Module (ASY-M8250-FIL). If fault and/or motion outputs need to be directly wired to field devices, an output module (such as, ASY-M8250-XOUT) must be used in place of the filler module. Consult Autotech for specifications on output module. Card Location: Uses one or two slots (any location) in an 1/0 rack. PLC Communication: Command-based communication using standard program controller logic. Power Requirements: Backplane: 5 VDC @ 650mA Customer (Input Power): 24 VDC ± 100mA Environment Conditions: Operating Temperature: -10°F to +130ºF (-23ºC to +55ºC) Relative Humidity: 5 to 95% non-condensing RESOLVER INTERFACE: Position Transducer: Autotech's series RL 100, E7R, E8R, or RLI 01, RL500 or equivalent resolvers. Cable Length between Resolver and M8350: 2500 feet max, shielded. Resolver Cable: Overall foil shielded, twisted pair, such as Autotech's cable (CBL-1 OT22-xxxx). PROGRAMMING: All features programmable from keypad or through backplane. Scale Factor: Programmable from 19 to 4095 (Resolution 20-4096 counts per turn). |
![]() |
Offset: Programmable from 0 to scale factor value. CONTROL INPUTS: |