Input Power:
11-28 VAC, 6 W
Operating Temperature: -10 °F to +130 °F (-23 °C
to +55 °C)
Position Transducer: AVG Automation's single turn
resolver such as RL100, RL101, RL500, RL501, E1R, E7R, E8R, or E9R
series
Maximum Cable Length Between Resolver and DM2: 2500
ft, shielded
Output Formats: Factory scale quadrature
Output Type:
P: PNP sourcing:
Logic TRUE: Transistor ON,
1.7 V drop @ 100 mA
Logic FALSE: Transistor OFF,0.2 mA
leakage @50 VDC
N: NPN sinking (LOW TRUE LOGIC):
Logic TRUE: Transistor ON,
1.1 V max @ 100 mA
Logic FALSE: Collector open, 0.1
mA leakage @50VDC
C: NPN sinking (HIGH TRUE LOGIC):
Logic TRUE: Collector open,
0.1 mA leakage @50 VDC
Logic FALSE: 1.1 V drop @ 100 mA
T: TTL output, 5V logic with multiplexing:
Logic TRUE: 3.00 mA max, 2V
min.
Logic FALSE: 24.0 mA max, 0.8V max |
 |
Transparent:
Output data is continuously updated. The data is latched for
100 +/- 10 usec within 30 usec of a transfer input.
PC Handshake: Edge triggered (Low to high as well as
high to low); 30 usec minimum strobe width; the data is stabilized
within 100 usec of any triggering edge, and remains frozen until
next triggering edge comes in.
Slave Systems: Slave units must be used in
conjunction with an Autotech Master Unit. They cannot be
used as stand-alone units. Up to seven slaves may be added
to one master unit. The slave shares the position transducer
with the master. |